Alarms
Caution!
Increasing the threshold from this factory default setting may prevent the unit
generating an alarm during a fan failure or air-conditioning failure event.
4.4.6 PSU Alarms
The EQ8096 utilizes up to 2 Hot-swappable PSUs and supports PSU failure
detection for each PSU fitted.
When dual-redundant PSUs are fitted (option EQ8096/HWO/DPS), the power
supplies operate in a load-shared scheme. In the rare event of a PSU failure, the
remaining PSU will provide power to the unit. In this situation, an alarm will be raised
and the PSU unit should be replaced as soon as possible.
When the unit is operating with a single PSU, the Alarm status page will show this
as ‘not fitted’ as shown in Figure 4.8.
Figure 4.8 PSU Alarms Web Page
4.5 Trap Destination Table
Figure 4.9 shows the Trap (alarm) Destination web page. The Simple Network
Management Protocol (SNMP) Trap addresses are set here. Once the addresses of
the SNMP servers are entered, any alarms will be broadcast to all destinations. The
EQ8096 maintains a list of the last 20 reported alarms (traps) and makes it available
to the SNMP management system.